Underwriters Laboratories Inc. UL 50 and UL 508
Indoor use to provide a degree of protection against contact with the enclosed equipment and against a limited amount of falling dirt
Canadian Standards Association CSA Standard C22.2 No 94
General purpose enclosure; protects against accidental contact with live parts
NEMA Type 2Underwriters Laboratories Inc. UL 50 and UL 508
Indoor use to provide a degree of protection against limited amounts of falling water and dirt
Canadian Standards Association CSA Standard C22.2 No 94
Drip proof enclosure same as Type 1; indoor use to provide a degree of protection against dripping and light splashing of non-corrosive liquids and falling dirt
NEMA Type 3Underwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure
Canadian Standards Association CSA Standard C22.2 No 94
Weatherproof enclosure; indoor or outdoor use to provide a degree of protection against rain, snow and blown dust; undamaged by the external formation of ice on the enclosure
NEMA Type 3RUnderwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure
Canadian Standards Association CSA Standard C22.2 No 94
Weather proof enclosure; indoor or outdoor use to provide a degree of protection against rain or snow; undamaged by the external formation of ice on the enclosure (CSA does not specify sleet resist)
NEMA Type 3SUnderwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against windblown dust, rain and sleet; external mechanisms remain operable while ice laden
Canadian Standards Association CSA Standard C22.2 No 94
Weather proof enclosure; indoor or outdoor use to provide a degree of protection against rain or snow; undamaged by the external formation of ice on the enclosure surface (CSA does not specify sleet proof)
NEMA Type 4Underwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against splashing water, windblown dust and rain, and hose directed water; undamaged by the formation of ice on the enclosure
Canadian Standards Association CSA Standard C22.2 No 94
Watertight enclosure; indoor or outdoor use to provide a degree of protection against rain, snow, blown dust, splashing and hose directed water; undamaged by the external formation of ice on the enclosure
NEMA Type 4XUnderwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against splashing water, windblown dust and rain, and hose directed water; undamaged by the formation of ice on the enclosure; resists corrosion
Canadian Standards Association CSA Standard C22.2 No 94
Watertight enclosure; indoor or outdoor use to provide a degree of protection
against rain, snow, blown
dust, splashing and hose directed water; undamaged by the external formation
of ice on the enclosure; resists corrosion
Underwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against the entry of water during temporary submersion at a limited depth; undamaged by the formation of ice on the enclosure
Canadian Standards Association CSA Standard C22.2 No 94
No CSA equivalent
NEMA Type 6PUnderwriters Laboratories Inc. UL 50 and UL 508
Indoor or outdoor use to provide a degree of protection against the entry of water during prolonged submersion at a limited depth
Canadian Standards Association CSA Standard C22.2 No 94
No CSA equivalent
NEMA Type 12Underwriters Laboratories Inc. UL 50 and UL 508
Indoor use to provide a degree of protection against dust, falling dirt and dripping non-corrosive liquids No knockouts
Canadian Standards Association CSA Standard C22.2 No 94
Indoor use to provide a degree of protection against circulating dust, lint, fibers, dripping and light splashes of non-corrosive liquids
NEMA Type 13Underwriters Laboratories Inc. UL 50 and UL 508
Indoor use to provide a degree of protection against dust and spraying of water, oil and non-corrosive coolants
Canadian Standards Association CSA Standard C22.2 No 94
Indoor use to provide a degree of protection against circulating dust, lint, fibers, seepage and spraying of non-corrosive liquids including oils and coolants